IC60H – miniature circuit breaker – 2P – 25A – C curve A9F84225
device application |
Distribution
|
|
---|---|---|
range |
Acti 9
|
|
product name |
Acti 9 iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60H
|
|
poles description |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
25Â A
|
|
network type |
AC
DC |
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000Â A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 10Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 30Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15Â kA Icu at <= 125 V DC conforming to EN/IEC 60947-2 42Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
standards |
EN 60898-1
EN 60947-2 IEC 60898-1 IEC 60947-2 |
network frequency |
50/60 Hz
|
|
---|---|---|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
15Â kA 50Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 50Â % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz 5Â kA 50Â % conforming to EN 60947-2 – 440 V AC 50/60 Hz 15Â kA 50Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 7.5Â kA 50Â % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz 5Â kA 50Â % conforming to IEC 60947-2 – 440 V AC 50/60 Hz 7500Â A 75Â % conforming to EN 60898-1 – 400 V AC 50/60 Hz 7500Â A 75Â % conforming to IEC 60898-1 – 400 V AC 50/60 Hz 21Â kA 50Â % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz 21Â kA 50Â % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz 15Â kA 100Â % conforming to IEC 60947-2 – 72…125 V DC 15Â kA 100Â % conforming to EN 60947-2 – 72…125 V DC |
|
limitation class |
3 conforming to EN 60898-1
3 conforming to IEC 60898-1 |
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to EN 60947-2
6Â kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
4
|
|
height |
85Â mm
|
|
width |
36Â mm
|
|
depth |
78.5Â mm
|
|
net weight |
0.25Â kg
|
|
colour |
White
|
|
mechanical durability |
20000Â cycles
|
|
electrical durability |
10000Â cycles
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14Â mm for top or bottom connection
|
|
tightening torque |
2Â N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
₦14,800.00
Compare-
ACCESSORIES, ELECTRICAL FITTINGS, Electro, SOCKETS, SOCKETS & SWITCHES
BG ELECTRICAL 855RCD 13A RCD FUSED CONNECTION UNIT
ACCESSORIES, ELECTRICAL FITTINGS, Electro, SOCKETS, SOCKETS & SWITCHESBG ELECTRICAL 855RCD 13A RCD FUSED CONNECTION UNIT
BG Electrical 855RCD 13A RCD Fused Connection Unit
Features
- Maximum load 3120 watts 240V AC
- 30 mA trip speed 40 ms
- Latching type
- Terminal capacity 3 x 2.5mm², 2 x 4.0mm² & 1 x 6.0mm²
- Manufactured to BS 7288:1990
- 855RCD – Minimum mounting box depth 35mm
- 10mm Spacer provded for shallow boxes
SKU: n/a -
FLUORESCENT CHOKE, LED DRIVERS
TB60I 230 (10 – 60 W Electronic Transformer)
DescriptionTrailing -edge phase control
Average service life 30,000 h
Operating ambient temperature -20°C – +50°CProtection:
1. Short- & open circuit proof
2. Auto. overheat regulation or cut off
3. Overload protection
4. SELVSKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit breaker, Easy9, 3P, 32 A, C curve, 6000 A EZ9F56332
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit breaker, Easy9, 3P, 32 A, C curve, 6000 A EZ9F56332
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 3Pnumber of protected poles 3[In] rated current 32Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000Â A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000Â A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50 Hz[Ue] rated operational voltage 220 V AC 50/60 Hz
400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 6height 81 mmwidth 54 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² flexible
Tunnel type terminal (top or bottom) 1…35 mm² rigidtightening torque 3.5 N.m top or bottomSKU: n/a -
Electro, SOCKETS & SWITCHES, SWITCHES
BG FBS74 – 45AMP WATER HEATER SWITCH
45A Rated
Easy to install, supplied with fixing screws and installation instructions
Ideal for cookers and ovens
Double Pole switching for the peace of mind of a safer installation
Twin earth fitted as standard for high integrity circuits
Captive screws prevent screw loss
Flush power indicator
Screwless front plate clips on and off easily and has a sleek, flat profile, with no visible plastic around the switch.
Moisture control gasket, prevents tarnishing from new plaster