IC60H – miniature circuit breaker – 2P – 32A – C curve A9F84232
device application |
Distribution
|
|
---|---|---|
range |
Acti 9
|
|
product name |
Acti 9 iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60H
|
|
poles description |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
32Â A
|
|
network type |
DC
AC |
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000Â A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 10Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 30Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15Â kA Icu at <= 125 V DC conforming to EN/IEC 60947-2 42Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
standards |
EN 60898-1
IEC 60898-1 EN 60947-2 IEC 60947-2 |
network frequency |
50/60 Hz
|
|
---|---|---|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
15Â kA 50Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 50Â % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz 5Â kA 50Â % conforming to EN 60947-2 – 440 V AC 50/60 Hz 15Â kA 50Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 7.5Â kA 50Â % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz 5Â kA 50Â % conforming to IEC 60947-2 – 440 V AC 50/60 Hz 7500Â A 75Â % conforming to EN 60898-1 – 400 V AC 50/60 Hz 7500Â A 75Â % conforming to IEC 60898-1 – 400 V AC 50/60 Hz 21Â kA 50Â % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz 21Â kA 50Â % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz 15Â kA 100Â % conforming to IEC 60947-2 – 72…125 V DC 15Â kA 100Â % conforming to EN 60947-2 – 72…125 V DC |
|
limitation class |
3 conforming to EN 60898-1
3 conforming to IEC 60898-1 |
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to EN 60947-2
6Â kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
4
|
|
height |
85Â mm
|
|
width |
36Â mm
|
|
depth |
78.5Â mm
|
|
net weight |
0.25Â kg
|
|
colour |
White
|
|
mechanical durability |
20000Â cycles
|
|
electrical durability |
10000Â cycles
|
|
connections – terminals |
Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexible |
|
wire stripping length |
14Â mm for top or bottom connection
|
|
tightening torque |
3.5Â N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
₦14,800.00
Compare-
CHINT
CHINT NU6-â…¡G/F Low-voltage Surge Arrester 15 – 40kA
NU6-â…¡G/F Low-voltage Surge Arrester
- Certificates: international certificates are under proceeding;
- Number of poles: 1, 2,3, 4;
- Electric ratings: 230/400V, AC50Hz;
- Application: Protect electric system and on-loading electrical apparatus from thunder and instantaneous over-voltage;
- Standard: IEC 61643-1, EN 61643-11
SKU: n/a -
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONS
Ultimate Screwless flat plate – rocker plate switch – 1 gang – stainless steel GU1412WSS
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONSUltimate Screwless flat plate – rocker plate switch – 1 gang – stainless steel GU1412WSS
Main range of product Ultimaterange Ultimateaesthetic name Screwless flat plateproduct or component type Plate switchcontrol type Rockerswitch function 1-pole 2-wayrated current 16 AX at 230 V ACComplementary connections – terminals Screw terminalsmaterial Steelquantity per set Set of 1number of gangs 1 gangdevice mounting Wall mountedheight 88Â mmwidth 88Â mmdepth 24Â mmSKU: n/a -
Electro, SCHNEIDER SECTIONS, Schneider Thorsman Testmeters
Thorsman Multifunction Cable Tracer IMT23106
Electro, SCHNEIDER SECTIONS, Schneider Thorsman TestmetersThorsman Multifunction Cable Tracer IMT23106
Main range Thorsmanproduct or component type Multi-function wire tracersupply Receiver 4 battery 1.5 V LR41/SR41
Transmitter 2 battery 1.5 VComplementary device composition Transmitter – to generate a distinct tone in wire
Receiver – to pick up the tonelocal signaling LED operatinglanguage English
Danish
Swedish
Finnish
Norwegianheight 183Â mmwidth 80Â mmdepth 46Â mmnet weight 220Â g with batterySKU: n/a -
ACCESSORIES, ELECTRICAL INDUSTRIAL, SOLAR POWERED
Solar Powered Water Pump DC 210W 80m
Product Name 210w 24v 50m dc brushless solar powered borehole water pump Model TB3IN-210/24/80/1.5/0.75 Material stainless steel Color sliver Voltage(V) DC-36 Flow(m³/h) 1.5 Head(m) 80 Solar(W) 200 Voltrange(V) 21-50 Outlet(IN) 0.75 SKU: n/a -
Electro, INDOOR LIGHTS, LED LIGHTS, LIGHT BULBS, LIGHTING
WINWIN POP Reccessed LED Panel light 18watt
Electro, INDOOR LIGHTS, LED LIGHTS, LIGHT BULBS, LIGHTINGWINWIN POP Reccessed LED Panel light 18watt
Rated Power(W): 3/6/9/12/15/18/24W
Size: Φ85*22mm/Φ120*22mm/Φ145*22mm/Φ174*22mm/Φ200*22mm/Φ225*40mm/Φ300*40mm
Cut out Size: Φ65mm/Φ100mm/Φ125mm/Φ155mm/Φ180mm/Φ200mm/Φ280mm
Input Voltage(V): AC85-265V
LED Type: SMD
Lumen(LM): 65-80LM/W
Frequency Range(Hz): 50-60Hz
Beam angle(Degree): 180°
Color Temperature(K): 2700K-6500K
CRI(Ra): >70
Power factor(PF): >0.55
LED Chip Brand: San’an
Material: Aluminum
Working Temperature: -20℃~+45℃SKU: n/a -
ELECTRICAL INDUSTRIAL, TRANSFORMER
BETA 1000KVA/33/0.415V COPPER/COPPER WINDING TRANSFORMER
Produced within a power range between 10 – 100.000 kVA , up to 170 kV high voltage level, three phase or single phase, oil immersed, ONAN, ONAF, OFWF, with Off-Load or On-Load Tap Changer, used both external and internal.
Dimensions of transformer conservator are determined and designed after several heat calculations of the oil stored in expansion tank and oil level changes by heat.
Being open to atmosphere, oil pressure changes continuously in Conservator Type Transformers due to thermal effects and exchange of air is dehumidified via air breather silicagel.SKU: n/a