Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 4 A, C curve, 10000 A (IEC 60898-1), 70 kA (IEC 60947-2) A9F84204
device application |
Distribution
|
|
---|---|---|
range |
Acti 9
|
|
product name |
Acti 9 iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60H
|
|
poles description |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
4 A
|
|
network type |
AC
DC |
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2 70 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
standards |
IEC 60947-2
IEC 60898-1 EN 60947-2 EN 60898-1 |
|
quality labels |
NF
|
network frequency |
50/60 Hz
|
|
---|---|---|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
70 kA 100 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
70 kA 100 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 70 kA 100 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz 70 kA 100 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz 7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz 7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz 70 kA 100 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz 70 kA 100 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz 50 kA 100 % conforming to EN 60947-2 – 440 V AC 50/60 Hz 50 kA 100 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz 15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC 15 kA 100 % conforming to EN 60947-2 – 72…125 V DC |
|
limitation class |
3 conforming to EN 60898-1
3 conforming to IEC 60898-1 |
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
4
|
|
height |
85 mm
|
|
width |
36 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.25 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
2 N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
₦12,999.00
Compare-
Electro, SOCKETS, SOCKETS & SWITCHES
BG BRASS GEORGIAN PLUG SOCKET SWITCHED DOUBLE (2 GANG) NBG21B-01
Electro, SOCKETS, SOCKETS & SWITCHESBG BRASS GEORGIAN PLUG SOCKET SWITCHED DOUBLE (2 GANG) NBG21B-01
BRASS GEORGIAN PLUG SOCKET SWITCHED DOUBLE (2 GANG)
AT A GLANCE…- Top quality Brass finish – lightly lacquered to prevent finger marks
- Matching Brass rocker switch
- White plastic insert
- Specification: 2 gang, 13 amp (13AX)
- Requires a 25mm metal wall box
- Supplied with colour coded fixing screws
SKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
Lisse – Universal dimmer – 1 gang – 2 way – 400W/VA GGBL6012CS
Main range Lisseaesthetic name White mouldedproduct or component type Dimmerdevice presentation Complete productload type 230 V AC halogen lamp
Incandescent lamp: 400 Wcolour tint White mattquantity per set Set of 1Complementary device mounting Wall mounteddimmer application Inductive load
Resistive load[Ue] rated operational voltage 230 V AC 50 Hznumber of gangs 1 gangmaterial Urea (carbamide)connections – terminals Screw terminalsfixing mode By screws M3.5 x 25 mmtype of packing Bagheight 87 mmwidth 87 mmdepth 43.6 mmnet weight 0.072 kgSKU: n/a -
ACCESSORIES, ELECTRICAL INDUSTRIAL, Electro, RECLINE CABLES
Cometstar Nigeria Cable NAY 4 X 50.0MM
The construction and material are determined by three main factors:
• Working voltage, determining the thickness of the insulation;
• Current-carrying capacity, determining the cross-sectional size of the conductor(s);
• Environmental conditions such as temperature, water, chemical or sunlight exposure, and mechanical impact, determining the form and composition of the outer cable jacketSKU: Cometstar Nigeria Cable NAY 4 X 50.0MM -
Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC100F3020 – Circuit breaker Easypact EZC100F – TMD – 20 A – 3 poles 3d
Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC100F3020 – Circuit breaker Easypact EZC100F – TMD – 20 A – 3 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Fcircuit breaker name Easypact EZC100Fdevice application Distributionpoles description 3Pprotected poles description 3tnetwork type DC
ACnetwork frequency 50/60 Hz[In] rated current 100 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Fbreaking capacity 25 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
5 kA Icu at 125 V DC 1P conforming to IEC 60947-2
5 kA Icu at 250 V DC 2P conforming to IEC 60947-2
5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 125 V DC conforming to IEC 60947-2
2.5 kA at 250 V DC conforming to IEC 60947-2
2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2
5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
3.75 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 20 A at 50 °Cprotection type Short-circuit protection
Overload protectionpollution degree 3 conforming to IEC 60664-1
3 conforming to IEC 947-1SKU: n/a -
There are no reviews yet.