Miniature circuit-breaker, Acti9 iC60H, 2P, 6 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84206
device application |
Distribution
|
|
---|---|---|
range |
Acti 9
|
|
product name |
Acti 9 iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60H
|
|
poles description |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
6 A
|
|
network type |
DC
AC |
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2 42 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
standards |
IEC 60947-2
IEC 60898-1 EN 60947-2 EN 60898-1 |
network frequency |
50/60 Hz
|
|
---|---|---|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
15 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz 5 kA 50 % conforming to EN 60947-2 – 440 V AC 50/60 Hz 15 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 7.5 kA 50 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz 5 kA 50 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz 7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz 7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz 21 kA 50 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz 21 kA 50 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz 15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC 15 kA 100 % conforming to EN 60947-2 – 72…125 V DC |
|
limitation class |
3 conforming to EN 60898-1
3 conforming to IEC 60898-1 |
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
4
|
|
height |
85 mm
|
|
width |
36 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.25 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
2 N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
₦24,500.00
Compare-
SOLAR POWERED
FANGPUSUN MPPT CHARGE CONTROLLER 80A
Product features
1.Increases PV Array Output by up to 30%
2.Advanced Continuous Maximum Power Point Tracking
3.Full Power Output in Ambient Temperatures up to 104°F (40°C)
4.Battery Voltages from 12 VDC to 60 VDC
5.Programmable Auxiliary Control Output
6.Built-in 128 days of Data Logging
7.Fully Network Integrated and ProgrammableDisplays
1.Text LCD display for operating parameters,fault messages,self testOptions
1.Menu-driven operation
2.Programming by buttonsCertificates
1.Compliant with European Standards(CE)
2.RoHS compliant
3.ISO 9001SKU: n/a -
CHANGEOVER SWITCHES
Santon 600Amps Changeover Switch
Santon produce 3 ranges of manual changeover switches, the Packet, Cam and Flat pack types. The Packet and Cam can be provided with or without off position and are available enclosed or as an open type for mounting in customers equipment, i.e. contol panels etc.
SKU: PT600 -
Electro, Schneider Mureva Floodlight, SCHNEIDER SECTIONS
Thorsman, Worklight 30W, IP65 DK Plug 230V IMT47230
Electro, Schneider Mureva Floodlight, SCHNEIDER SECTIONSThorsman, Worklight 30W, IP65 DK Plug 230V IMT47230
Main range Thorsmanrange of product Thorsman Worklightsproduct name Worklightproduct or component type Lampdevice application Mobile equipment
Ware-houses and parking garages
Hospital
Residential
Sports hallComplementary type of installation Outdoor[Ue] rated operational voltage 230 Vnetwork type ACoperational power in W 30 Wplug standard Denmarkluminous flux 3000 lmbulb lifespan 50000 hcolour rendering index Ra=80colour temperature 4000 Kbeam angle 110 °power factor 0.9height 254.5 mmwidth 231.0 mmdepth 20.0 mmnet weight 1.1 kgSKU: n/a
There are no reviews yet.