Miniature circuit breaker, Easy9, 2P, 16 A, C curve, 6000 A EZ9F56216
range |
Easy9
|
|
---|---|---|
device application |
Distribution
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
Easy9 MCB
|
|
Poles |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
16Â A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000Â A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000Â A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1 |
|
suitability for isolation |
Yes conforming to IEC 60898-1
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
220 V AC 50/60 Hz
400 V AC 50/60 Hz |
|
magnetic tripping limit |
5…10 x In
|
|
[Ics] rated service breaking capacity |
6Â kA 100Â % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Uimp] rated impulse withstand voltage |
4Â kV conforming to IEC 60898-1
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Without
|
|
mounting mode |
Clip-on
|
|
mounting support |
DIN rail
|
|
9 mm pitches |
4
|
|
height |
81Â mm
|
|
width |
36Â mm
|
|
depth |
66.5Â mm
|
|
colour |
Grey (RAL 7035)
|
|
mechanical durability |
10000Â cycles
|
|
electrical durability |
4000Â cycles
|
|
connections – terminals |
Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexible |
|
tightening torque |
2Â N.m top or bottom
|
|
earth-leakage protection |
Without
|
₦7,600.00
Compare-
CIRCUIT BREAKERS
IC60N – miniature circuit breaker – 3P – 63A – C curve
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 3Pnumber of protected poles 3[In] rated current 63Â Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6000Â A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
36Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
20Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
6Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
36Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Â kA Icu at <= 180 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
EN 60947-2
IEC 60898-1
IEC 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15Â kA 75Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 75Â % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
4.5Â kA 75Â % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15Â kA 75Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 75Â % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5Â kA 75Â % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
27Â kA 75Â % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
27Â kA 75Â % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
6000Â A 100Â % conforming to EN 60898-1 – 400 V AC 50/60 Hz
6000Â A 100Â % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
10Â kA 100Â % conforming to IEC 60947-2 – 125…180 V DC
10Â kA 100Â % conforming to EN 60947-2 – 125…180 V DC[Ui] rated insulation voltage 500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6Â kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 6height 85 mmwidth 54 mmdepth 78.5 mmnet weight 0.375 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
Schneider Mureva Floodlight, SCHNEIDER SECTIONS
Mureva lights, Floodlight 200W, IP65 230V IMT47223
Main range Murevarange of product Mureva lightsproduct name Floodlightproduct or component type Lampdevice application Ware-houses and parking garages
Residential
Media device support
Public areas
Secure lighting
Stadiums and arenasComplementary type of installation OutdoorTotal system power 200 Wlight source LED[Ue] rated operational voltage 230 V ACpower factor 0.9colour rendering index Ra=80luminous flux 20000 lmbulb lifespan 50000 hcolour temperature 6500 Kcolour Blackprovided equipment Sensorbeam angle 110 °shape Rectangularheight 342.0 mmwidth 278.0 mmdepth 61.0 mmnet weight 4.9 kgSKU: n/a -
COMPUTING, LAPTOPS
HP 15 i3 1tb 4gb touch screen win10
Key Features
- 7th Gen Intel Core i3-7020U processor, 2.3GHz base processor speed, 2 cores, 3MB cache
- Windows 10 Home
- 15.6-inch HD WLED Touch Screen Display
- 4GB DDR4 RAM | Storage: 1TB HDD, 5400 RPM | Intel HD Graphics 620
- Max battery life = up to 13 hours
- 1 HDMI, 2 USB 3.0, 1 USB 2.0, 1 Audio-output | With CD drive
SKU: n/a -
CHINT
NX8 – MCB CHINT . ELECTRIC BOX 20way
The MCB CHINT NX8 plastic electrical cabinet box is compact, sturdy, and has a high finish.
Can be used as a wall cabinet or used as a floating cabinet due to its versatile design. There are error lights, power failure.
ABS plastic helps to withstand factors such as heat, sunlight, increasing the life of the cabinet. The lid of the cabinet is made of transparent PC plastic, making it easy to see the equipment inside. Available with 4-sided wiring hole.
Standard DIN Rail, convenient to connect and install equipment
Parameters of MCB CHINT NX8 . plastic electrical cabinet box
- Material: ABS/PC . plastic
- Type: Wall mounted plastic electrical cabinet
- Protection level: IP30
- Meets standards: IEC/EN 60439-3 (IEC/EN 60670-24)
- Application: in civil electricity, industrial electricity, solar power
SKU: n/a -
ELECTRICAL INDUSTRIAL, TRANSFORMER
MEKSAN Transformer 750kVA 11/415kV
Meksan Transformer manufacture distribution and power transformer from 50 kVA up to 50 MVA.  Our products are produced in accordance with the TS 267 and the IEC60076  standards. Our production is documented with the TSE (Türkish Standard Institue) standards confortmity, ISO 9001:2000 quality system and ISO 14001 environmental management system certificates.
SKU: n/a -
ACCESSORIES, ELECTRICAL INDUSTRIAL, Electro, RECLINE CABLES
Cometstar Nigeria Cable NAY 4 X 50.0MM
The construction and material are determined by three main factors:
• Working voltage, determining the thickness of the insulation;
• Current-carrying capacity, determining the cross-sectional size of the conductor(s);
• Environmental conditions such as temperature, water, chemical or sunlight exposure, and mechanical impact, determining the form and composition of the outer cable jacketSKU: Cometstar Nigeria Cable NAY 4 X 50.0MM