Cap-Base E40 [ E40]Operating Position UNIVERSAL [ Any or Universal (U)]Life to 5% Failures (Nom) 12000 hLife to 20% Failures (Nom) 20000 hLife to 50% Failures (Nom) 28000 hSystem Description External Ignitor - Light Technical
-
Color Code 220 [ CCT of 2000K]Luminous Flux (Rated) (Min) 43200 lmLuminous Flux (Rated) (Nom) 48000 lmLumen Maintenance 2000 h (Min) 94 %Lumen Maintenance 2000 h (Nom) 97 %Lumen Maintenance 5000 h (Min) 88 %Lumen Maintenance 5000 h (Nom) 94 %Correlated Color Temperature (Nom) 2000 KLuminous Efficacy (rated) (Nom) 123 lm/WColor Rendering Index (Max) 25Color Rendering Index (Nom) – - Operating and Electrical
-
Power (Nom) 392.0 WLamp Current (EM) (Nom) 4.6 AIgnition Supply Voltage (Max) 198 VIgnition Peak Voltage (Max) 2800 VRe-Ignition Time (Min) (Max) 120 sIgnition Time (Max) 5 sVoltage (Max) 115 VVoltage (Min) 85 VVoltage (Nom) 100 V - Controls and Dimming
-
Dimmable YesRun-Up Time 90% (Max) 5 min - Mechanical and Housing
-
Bulb Finish ClearCap-Base Information – - Approval and Application
-
Energy Efficiency Label (EEL) A+Mercury (Hg) Content (Nom) 24.5 mgEnergy Consumption kWh/1000 h 431 kWh - Luminaire Design Requirements
-
Bulb Temperature (Max) 450 °CCap-Base Temperature (Max) 250 °C - Product Data
-
Full product code 871829121292800Order product name SON-T 400W E E40 SL/12EAN/UPC – Product 8718291212928Order code 928487300098Numerator – Quantity Per Pack 1Numerator – Packs per outer box 12Material Nr. (12NC) 928487300098Net Weight (Piece) 0.181 kg
₦0.00
Compare-
LIGHT SWITCHES & ELECTRICAL SOCKETS
13A 250V 1 Gang Switched Socket with Neon KB15N
Main range Vivaceproduct or component type Socket-outlet with switchdevice short name KB15device presentation Complete mechanismComplementary pilot light Red neon indicatoroutlet poles configuration 2P + Enumber of gangs 1 gangColour tint Whitematerial Polycarbonate: grid plate
Polycarbonate: surround
Polycarbonate: baseprojecting depth 8 mmdevice mounting Flushmounting support Wall mountedfixing mode By screw M3.5fixing center 60.3 mmembedding depth 35 mmrated current 13 A at 250 V AC, resistivenetwork frequency 50 Hzcontacts material Brass and phosphor bronzeconnections – terminals Pillar terminalterminal identifier N
L
Earthtightening torque 0.4 N.mclamping connection capacity 2 x 4 mm²
3 x 2.5 mm²width 87 mmheight 87 mmSKU: n/a -
CHINT
CHINT NXM Series 2,3,4 Pole Moulded Case Circuit Breakers MCCB
The moulded case circuit breaker will provide protection for the circuit and equipment in case of overload, short circuit and under voltage condition occurred in the power distribution circuit. Besides, it can also provide protection of overload, short circuit and under voltage for the non-frequent start of motor
DESCRIPTION
- Compliance To IEC/EN60947-2
- Frame size: NXM series mould case circuit breaker: 63A, 125A, 160A, 250A, 400A, 630A, 800A, 1000A, 1250A, 1600A
- Release type: thermal magnetic fixed type; magnetic fixed type; electronic type
- Installation method: Fixed type; plug-in type
- Number of poles: 2P, 3P, 4P
- Rated operational voltage: Ue (VAC): 220, 415
- ICU: 25KA
- The brand-new electronic release Manage fault accurately Operate more efficiently and reliably
- Built-in busbar temperature sensor, to control every aspect. Select the most suitable frame size, increase the product cost performance and reduce costs of using.
- The brand-new electronic release, provide more accurate circuit protection. The all-new electronic release can deal with the hidden fault more accurately, with a more convenient parameters setting.
- Dual insulation design, for a more convenient maintenance. Enhance the insulating capacity of the product, allowing the accessories installation, which make the maintenance more safe and efficient.
- With a USB port for better human-machine interaction. Connected with PC devices through the USB port, lets you manage functions such as data reading, parameter setting, on-line detection and failure recording.
- Absolute adaptability, with steady and reliable operation in extreme conditions. -35°C/+70°operating temperature range.
SKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
IC60H – miniature circuit breaker – 2P – 25A – C curve A9F84225
Schneider Circuit Breakers, SCHNEIDER SECTIONSIC60H – miniature circuit breaker – 2P – 25A – C curve A9F84225
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 25 Anetwork type AC
DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
42 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
EN 60947-2
IEC 60898-1
IEC 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
21 kA 50 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC
15 kA 100 % conforming to EN 60947-2 – 72…125 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC100N4030 – Circuit breaker Easypact EZC100N – TMD – 30 A – 4 poles 3d
Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC100N4030 – Circuit breaker Easypact EZC100N – TMD – 30 A – 4 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Ncircuit breaker name Easypact EZC100Ndevice application Distributionpoles description 4Pprotected poles description 3tnetwork type AC
DCnetwork frequency 50/60 Hz[In] rated current 100 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Nbreaking capacity 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
5 kA Icu at 125 V DC 1P conforming to IEC 60947-2
5 kA Icu at 250 V DC 2P conforming to IEC 60947-2
5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2
18 kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 125 V DC conforming to IEC 60947-2
2.5 kA at 250 V DC conforming to IEC 60947-2
2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
9 kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 30 A at 50 °Cprotection type Overload protection
Short-circuit protectionpollution degree 3 conforming to IEC 60947Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 8500 cycleselectrical durability Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 25 mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 130 mmwidth 100 mmdepth 60 mmSKU: n/a -
-
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 4P 4A C Miniature Circuit breaker A9F44404
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 4P 4A C Miniature Circuit breaker A9F44404
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 4Pnumber of protected poles 4[In] rated current 4 Anetwork type AC/DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 50 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 50 kA 100 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
25 kA 100 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 8height 85 mmwidth 72 mmdepth 78.5 mmnet weight 0.5 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockEnvironment standards EN/IEC 60898-1
EN/IEC 60947-2IP degree of protection IP20 conforming to IEC 60529pollution degree 3 conforming to EN/IEC 60947-2tropicalisation 2 conforming to IEC 60068-1relative humidity 95 % at 55 °Cambient air temperature for operation -35…70 °Cambient air temperature for storage -40…85 °CSKU: n/a