CHINT
Voltage Monitoring Relay XJ3-D
XJ3 series phase failure phase sequence protection relay
www.finglai.comModel number ad parameters
Model number | XJ3-G | XJ3-S | XJ3-D |
Related product | Order | Order | Visiting… |
Phase failure protection | √ | √ | √ |
Phase wrong protection | √ | √ | √ |
Overvoltage protection | Χ | Χ | 380V-460V 1.5s-4s(Adjustable) |
Undervoltage protection | Χ | Χ | 300V-380V 2s-9s (Adjustable) |
Contact form | SPST-NO and SPST-NC | SPST-NO and SPST-NC | SPDT |
Action delay time | 2s max | 2s max | 2s max |
External dimensions | 85x46x110 mm | 85x46x110 mm | 70.5×45.5×115 mm |
Mounting type | Device or din rail | Device or din rail | 35mm din rail or punch |
Model number | XJ3 series |
Supply voltage | 380VAC 50Hz |
Contact rating | Ue/le AC-15 380V/0.95A Ith 5A |
Electrical life | 1×105 |
Mechanical life | 1×106 |
Operational temperature | -5°C-40°C |
₦16,500.00
Compare-
ACCESSORIES
APC ESSENTIAL SURGE ARREST 5 OUTLETS 230V – PM5-UK
The Essential SurgeArrest series offers a great value for home equipment and business applications such as small office/home computers
The APC will protect your equipment from the threat of bad power
Device Type Surge suppressor – external
Input Voltage AC 230 V/Frequency Required 50/60 HzSKU: APC 5outlet -
INDOOR LIGHTS, LED LIGHTS
U-MAX LED PanelLight 50Watt 6500K
LED Panel Light Features:
1. Wide input voltage design: Universal Use
2. Safe & reliable & pollution-free & non-toxic & harmless
3. Advanced PC material: anti-extrusion &non-friable
4. Super emitting angle: 120°
5. EMI anti-interference design
6. Constant current design
7. No Harmful Mercury, No UltraViolet or InfraRed RadiationSKU: n/a -
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONS
Ultimate Screwless flat plate – TV/FM socket – coaxial – 2 gangs GU7420BSS
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONSUltimate Screwless flat plate – TV/FM socket – coaxial – 2 gangs GU7420BSS
Main range of product Ultimateaesthetic name Screwless flat plateproduct or component type TV/FM socketTV socket type TV/FMquantity per set Set of 1Complementary radio connector Malenumber of gangs 2 gangsfixing mode By screwsmaterial Steelheight 88 mmwidth 88 mmdepth 24 mmSKU: n/a -
CIRCUIT BREAKERS
IC60N – miniature circuit breaker – 3P – 63A – C curve
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 3Pnumber of protected poles 3[In] rated current 63 Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
36 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at <= 180 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
EN 60947-2
IEC 60898-1
IEC 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15 kA 75 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 75 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
4.5 kA 75 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15 kA 75 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 75 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5 kA 75 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
27 kA 75 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
27 kA 75 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
6000 A 100 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
6000 A 100 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
10 kA 100 % conforming to IEC 60947-2 – 125…180 V DC
10 kA 100 % conforming to EN 60947-2 – 125…180 V DC[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 6height 85 mmwidth 54 mmdepth 78.5 mmnet weight 0.375 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a
There are no reviews yet.