Circuit breaker Easypact EZC100H – TMD – 63 A – 4 poles 3d
range of product |
EasyPact
|
|
---|---|---|
product or component type |
Circuit breaker
|
|
device short name |
Easypact EZC100H
|
|
circuit breaker name |
Easypact EZC100H
|
|
device application |
Distribution
|
|
poles description |
4P
|
|
protected poles description |
3t
|
|
network type |
AC
DC |
|
network frequency |
50/60 Hz
|
|
[In] rated current |
100 A at 40 °C
|
|
[Ui] rated insulation voltage |
690Â V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
|
breaking capacity code |
H
|
|
breaking capacity |
10Â kA Icu at 125 V DC 1P conforming to IEC 60947-2
10Â kA Icu at 250 V DC 2P conforming to IEC 60947-2 10Â kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100Â kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 20Â kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50Â kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 30Â kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2 30Â kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
5Â kA at 125 V DC conforming to IEC 60947-2
5Â kA at 250 V DC conforming to IEC 60947-2 5Â kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 2.5Â kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 15Â kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2 25Â kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 50Â kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 7.5Â kA at 415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
63 A at 50 °C
|
|
protection type |
Overload protection
Short-circuit protection |
|
pollution degree |
3 conforming to IEC 60947
|
control type |
Toggle
|
|
---|---|---|
mounting mode |
Fixed
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
mechanical durability |
8500Â cycles
|
|
electrical durability |
Category A: 1500Â cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
connection pitch |
25Â mm
|
|
local signalling |
Positive contact indication
|
|
neutral protection setting |
Without protection
|
|
earth-leakage protection |
Without
|
|
height |
130Â mm
|
|
width |
100Â mm
|
|
depth |
60Â mm
|
₦32,000.00
Compare-
ACCESSORIES, ELECTRICAL INDUSTRIAL, MOTOR STARTER
Consumer units Mistral65 transparent door 8M 1SL1201A00 25 – 32A MCBs
ACCESSORIES, ELECTRICAL INDUSTRIAL, MOTOR STARTERConsumer units Mistral65 transparent door 8M 1SL1201A00 25 – 32A MCBs
Consumer units Mistral65 transparent door 8M Dimensions WxHxD(mm): 232x250x154 ABB Code: 1SL1201A00 25 – 32A MCBs
General Information
-
- Extended Product Type:Â 65P08X12
-
- Product ID:Â Â 1SL1201A00
-
- ABB Type Designation:Â Mistral65
-
- EAN:Â Â 8000126097924
-
- Catalog Description:Â Â MISTRAL65 transp. door 8M
-
- Long Description:Â Â MISTRAL65 transparent door 8M
- Products » Low Voltage Products and Systems » Enclosures » Consumer Units » Consumer Units
SKU: n/a -
-
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 3P 40A C Miniature Circuit breaker A9F44340
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 3P 40A C Miniature Circuit breaker A9F44340
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 3Pnumber of protected poles 3[In] rated current 40Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6000Â A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
36Â kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
20Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
6Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Â kA Icu at 100…133 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27Â kA 75Â % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15Â kA 75Â % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 75Â % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5Â kA 75Â % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000Â A 100Â % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
15 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 6height 85 mmwidth 54 mmdepth 78.5 mmnet weight 0.375 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockEnvironment standards EN/IEC 60947-2
EN/IEC 60898-1IP degree of protection IP20 conforming to IEC 60529pollution degree 3 conforming to EN/IEC 60947-2tropicalisation 2 conforming to IEC 60068-1relative humidity 95 % at 55 °Cambient air temperature for operation -35…70 °Cambient air temperature for storage -40…85 °CSKU: n/a -
ELECTRICAL INDUSTRIAL, TRANSFORMER
ABB 33kV, 2500Amps SF6 Gas Circuit Breaker Outdoor Type OHB
Base Cabinet
The base cabinet is made of painted mild steel. The cabinet houses a spring operated mechanism which is mechanically linked to all three poles. The cabinet also includes the followings:- Anti-condensation heater
- Circuit breaker status indicator
- Mechanical operation counter
- Breaker control switches
- Anti-pumping relay
- AC / DC fuses, MCBs
- Auxiliary wiring
- Terminal blocks
- Gas pressure monitoring relays
Operating mechanism
For high operational reliability and minimal maintenance, a simple and robust spring operated mechanism is used.Features
- O-C-O operation without recharging
- Closing spring is charged by motor in less than 15 secs.
- Mechanical / electrical anti-pumping
- Provision for manual charging
- Suitable for rapid auto-reclosing
- Manual closing and tripping arrangement
- Mechanical ON – OFF and SPRING CHARGED indication
- Auxiliary switch: 13 NO + 13 NC
- Additional tripping solenoid(optional)
SKU: n/a -
COOKER UNIT, Electro, SOCKETS & SWITCHES
BG 45A DP Cooker Control Unit with 13A Socket and Power Indicators
COOKER UNIT, Electro, SOCKETS & SWITCHESBG 45A DP Cooker Control Unit with 13A Socket and Power Indicators
Product Information
- Double Pole switches manufactured to BS EN 60669-1
- Cooker Control Units manufactured to BS4177
- Minimum mounting box depth 47mm
- L&N terminal capacity 4 x 4.0mm², 3 x 6.0mm² & 1 x 16.0mm²
- E terminal capacity 3 x 4.00mm², 6 x 6.0mm² & 1 x 16.0mm²
SKU: n/a -
CABLE AND CABLE MANAGEMENT, Electro, SINGLE CORE WIRE
Doncaster Cables 6mm Single Core – Red
Product Description
Manufactured to BS 6004:2012 Table 3
Annealed Stranded Copper Conductor / PVC Insulated / PVC Sheathed. 300/500V
Designed for use in light industrial and domestic wiring. These cables are particularly suited for installation as meter tails and are intended for fixed installation in dry or damp premises.
These cables can be installed in conduit, in cable trunking and in cable ducting. Or where there is deemed little risk of mechanical damage these cables can be clipped direct, on cable tray, embedded or in free air. These cables are not intended to be laid underground.
Product Details
 Harmonisation Code Nominal Cross Sectional Area of Conductor (mm2) Nominal Stranding of Conductor (mm) Nominal Radial Thickness of insulation (mm) Nominal Radial Thickness of sheath (mm) Overall Diameter Lower Limit (mm) Overall Diameter Upper Limit (mm) Approximate Weight(kg/km) National Type 1.0 1 / 1.13 0.6 0.8 3.8 4.5 26 National Type 1.5 1 / 1.38 0.7 0.8 4.2 4.9 35 National Type 2.5 1 / 1.78 0.8 0.8 4.8 5.8 55 National Type 4.0 7 / 0.85 0.8 0.9 5.4 6.8 75 National Type 6.0 7 / 1.04 0.8 0.9 6.0 7.4 95 National Type 10.0 7 / 1.35 1.0 0.9 7.2 8.8 155 National Type 16.0 7 / 1.70 1.0 1.0 8.4 10.5 225 National Type 25.0 7 / 2.14 1.2 1.1 10.0 12.5 340 National Type 35.0 7 / 2.52 1.2 1.1 11.0 13.5 445 SKU: n/a
There are no reviews yet.