ACCESSORIES, ELECTRICAL INDUSTRIAL, MOTOR STARTER
Consumer units Mistral65 transparent door 4M 1SL1200A00
Consumer units Mistral65 transparent door 4M Dimensions WxHxD(mm): 152x202x117 (20A – 15A MCBs)
ABB Code: 1SL1200A00
Brand/ Manufacturer ABB
Manufacturer Part Number 1SL1200A00
Accessory type Transparent Door
For use with Consumer Unit
Length 117 mm
Width 152 mm
Height 202 mm
Ip rating IP65
₦48,500.00
Compare-
Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC100F3100 – Circuit breaker Easypact EZC100F – TMD – 100 A – 3 poles 3d
Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC100F3100 – Circuit breaker Easypact EZC100F – TMD – 100 A – 3 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Fcircuit breaker name Easypact EZC100Fdevice application Distributionpoles description 3Pprotected poles description 3tnetwork type DC
ACnetwork frequency 50/60 Hz[In] rated current 100 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Fbreaking capacity 25Â kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
5Â kA Icu at 125 V DC 1P conforming to IEC 60947-2
5Â kA Icu at 250 V DC 2P conforming to IEC 60947-2
5Â kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
10Â kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
10Â kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2
7.5Â kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 12.5Â kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
12.5Â kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
2.5Â kA at 125 V DC conforming to IEC 60947-2
2.5Â kA at 250 V DC conforming to IEC 60947-2
2.5Â kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
5Â kA at 380 V AC 50/60 Hz conforming to IEC 60947-2
5Â kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
3.75 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 100 A at 50 °Cprotection type Short-circuit protection
Overload protectionpollution degree 3 conforming to IEC 60664-1
3 conforming to IEC 947-1Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 8500Â cycleselectrical durability Category A: 1500Â cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 25Â mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 130Â mmwidth 75Â mmdepth 60Â mmEnvironment standards EN/IEC 60947-1
JIS C8201-2-2
GB/T 14048.2
EN/IEC 60947-2IP degree of protection IP20 conforming to IEC 60529IK degree of protection IK07 conforming to IEC 62262ambient air temperature for operation -25…70 °Cambient air temperature for storage -35…85 °CPacking Units Unit Type of Package 1 PCENumber of Units in Package 1 1Package 1 Weight 786 gPackage 1 Height 9.5 cmPackage 1 width 8.5 cmPackage 1 Length 14 cmUnit Type of Package 2 S02Number of Units in Package 2 12Package 2 Weight 9.887 kgPackage 2 Height 15 cmPackage 2 width 30 cmPackage 2 Length 40 cmUnit Type of Package 3 P06Number of Units in Package 3 192Package 3 Weight 166.692 kgPackage 3 Height 80 cmPackage 3 width 80 cmPackage 3 Length 60 cmSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 3P 4A C Miniature Circuit breaker A9F44304
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 3P 4A C Miniature Circuit breaker A9F44304
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 3Pnumber of protected poles 3[In] rated current 4Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 50Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
50Â kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
50Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
25Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
6000Â A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
15Â kA Icu at 100…133 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 50Â kA 100Â % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
50Â kA 100Â % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
50Â kA 100Â % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
25Â kA 100Â % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000Â A 100Â % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
15 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 6height 85 mmwidth 54 mmdepth 78.5 mmnet weight 0.375 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
-
ELECTRICAL FITTINGS, ELECTRICAL INDUSTRIAL, Electro, LIGHTING, SOLAR POWERED
Mornray SOLAR FLOOD LIGHT 200W
ELECTRICAL FITTINGS, ELECTRICAL INDUSTRIAL, Electro, LIGHTING, SOLAR POWEREDMornray SOLAR FLOOD LIGHT 200W
Solar Square Floodlight: Seven working modes for your convenience 1. Sensor mode 2. Half induction mode 3. 100% lighting mode 4. 50% lighting mode 5. 3 hour lighting mode 6. 5 hour lighting mode 7. 8 hour lighting mode Application: 1. Indoor use: indoor emergency lighting, home security lighting; 2. Outdoor use: courtyard lighting, landscape lighting, corridor lighting, door lighting, port lighting, container courtyard lighting, stadium lighting, courtyard lighting, plaza lighting, plant and beautification lighting, fountain waterscape lighting and other places; 3. Special event use: adventure lighting, camping lighting, fishing lighting, on-site maintenance lighting, barbecue lighting
SKU: n/a
There are no reviews yet.