Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC100N4032 Circuit breaker Easypact EZC100N – TMD – 32 A – 4 poles 3d
range of product |
EasyPact
|
|
---|---|---|
product or component type |
Circuit breaker
|
|
device short name |
Easypact EZC100N
|
|
circuit breaker name |
Easypact EZC100N
|
|
device application |
Distribution
|
|
poles description |
4P
|
|
protected poles description |
3t
|
|
network type |
DC
AC |
|
network frequency |
50/60 Hz
|
|
[In] rated current |
100 A at 40 °C
|
|
[Ui] rated insulation voltage |
690Â V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
|
breaking capacity code |
N
|
|
breaking capacity |
10Â kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 25Â kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 5Â kA Icu at 125 V DC 1P conforming to IEC 60947-2 5Â kA Icu at 250 V DC 2P conforming to IEC 60947-2 5Â kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 15Â kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2 18Â kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
5Â kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5Â kA at 125 V DC conforming to IEC 60947-2 2.5Â kA at 250 V DC conforming to IEC 60947-2 2.5Â kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5Â kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 12.5Â kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 9Â kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2 7.5Â kA at 415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
32 A at 50 °C
|
|
protection type |
Short-circuit protection
Overload protection |
|
pollution degree |
3 conforming to IEC 60947
|
control type |
Toggle
|
|
---|---|---|
mounting mode |
Fixed
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
mechanical durability |
8500Â cycles
|
|
electrical durability |
Category A: 1500Â cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
connection pitch |
25Â mm
|
|
local signalling |
Positive contact indication
|
|
neutral protection setting |
Without protection
|
|
earth-leakage protection |
Without
|
|
height |
130Â mm
|
|
width |
100Â mm
|
|
depth |
60Â mm
|
₦93,000.00
Compare-
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS
Lisse – Cooker Control Unit with 13A Socket LED Ind 45A DP Stainless Stl with Bl GGBL4001BSS
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETSLisse – Cooker Control Unit with 13A Socket LED Ind 45A DP Stainless Stl with Bl GGBL4001BSS
Main range Lisseaesthetic name Screwless decoproduct or component type Cooker control unitdevice presentation Complete productoutlet standard Britishquantity per set Set of 1Complementary number of gangs 2 gangsconnections – terminals Screw terminalsmaterial Stainless steeltype of installation Indoordepth 33Â mmwidth 148Â mmheight 87Â mmnet weight 0.286Â kgSKU: n/a -
CIRCUIT BREAKERS, DISTRIBUTION BOARDS, Electro
Easy9 miniature circuit breaker- 2P – 25 A – C curve – 6000 A – 230 V
CIRCUIT BREAKERS, DISTRIBUTION BOARDS, ElectroEasy9 miniature circuit breaker- 2P – 25 A – C curve – 6000 A – 230 V
Schneider Electric Easy9 Miniature Circuit Breaker- 2P – 6 A – C Curve – 6000 A – 230 V
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 2Pnumber of protected poles 2[In] rated current 25Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000Â A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000Â A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50/60 Hz[Ue] rated operational voltage 220 V AC 50/60 Hz
400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 4height 81 mmwidth 36 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexibletightening torque 2 N.m top or bottomearth-leakage protection WithoutEnvironment standards IEC 60898-1product certifications CEIP degree of protection IP20 conforming to IEC 60529pollution degree 2tropicalisation 2relative humidity 95 % at -5…60 °Cambient air temperature for operation -5…60 °Cambient air temperature for storage -40…85 °CSKU: n/a -
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS
Schneider 16AX 250V 2 Gang 2 Way Switch KB32
Main range Vivaceproduct or component type Switchdevice short name KB32device presentation Complete mechanismComplementary switch function 2-wayactuator Rockernumber of gangs 2 gangscolour tint Whitematerial Polycarbonate: grid plate
Polycarbonate: surround
Polycarbonate: baseprojecting depth 8Â mmdevice mounting Flushmounting support Wall mountedfixing mode By screw M3.5fixing center 60.3 mmembedding depth 35Â mmrated current 16 AX at 250 V AC, inductive
16 AX at 250 V AC, fluorescent[Ue] rated operational voltage 250 V ACnetwork frequency 50 Hzcontacts material Brass and phosphor bronzeconnections – terminals pillar terminalterminal identifier COM
L1
L2tightening torque 0.4 N.mclamping connection capacity 2.5 mm²width 87 mmheight 87 mmSKU: n/a -
CIRCUIT BREAKERS
IC60N – miniature circuit breaker – 3P – 63A – C curve
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 3Pnumber of protected poles 3[In] rated current 63Â Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6000Â A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
36Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
20Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
6Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
36Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Â kA Icu at <= 180 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
EN 60947-2
IEC 60898-1
IEC 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15Â kA 75Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 75Â % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
4.5Â kA 75Â % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15Â kA 75Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 75Â % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5Â kA 75Â % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
27Â kA 75Â % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
27Â kA 75Â % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
6000Â A 100Â % conforming to EN 60898-1 – 400 V AC 50/60 Hz
6000Â A 100Â % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
10Â kA 100Â % conforming to IEC 60947-2 – 125…180 V DC
10Â kA 100Â % conforming to EN 60947-2 – 125…180 V DC[Ui] rated insulation voltage 500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6Â kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 6height 85 mmwidth 54 mmdepth 78.5 mmnet weight 0.375 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS
Lisse – Switched Socket – 1 gang – 13A SP 2USB Polished Chrome with Black Inter GGBL30102USBABSSS
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETSLisse – Switched Socket – 1 gang – 13A SP 2USB Polished Chrome with Black Inter GGBL30102USBABSSS
Main range Lisseaesthetic name Screwless decoproduct or component type Switched socketdevice presentation Complete productoutlet standard Britishtype of packing BagComplementary switch function 1-poleactuator Rockernumber of gangs 1 gangfixing mode Concealed screwsconnections – terminals Screw terminalsmaterial Stainless steeltype of installation Indoordepth 32Â mmwidth 87Â mmheight 87Â mmnet weight 0.149Â kgSKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 1P 3A C Miniature Circuit breaker A9F44103
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 1P 3A C Miniature Circuit breaker A9F44103
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 1Pnumber of protected poles 1[In] rated current 3Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 50Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
50Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
50Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Â kA Icu at 12…48 V DC conforming to EN/IEC 60947-2
6Â kA Icu at 72 V DC conforming to EN/IEC 60947-2
6000Â A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 240 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 50Â kA 100Â % conforming to EN/IEC 60947-2 – 12…60 V AC 50/60 Hz
50Â kA 100Â % conforming to EN/IEC 60947-2 – 100…133 V AC 50/60 Hz
50Â kA 100Â % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
6000Â A 100Â % conforming to EN/IEC 60898-1 – 240 V AC 50/60 Hz
15Â kA 100Â % conforming to EN/IEC 60947-2 – 12…48 V DC
6 kA 100 % conforming to EN/IEC 60947-2 – 72 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.125 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a