IC60H – miniature circuit breaker – 1P – 32A – C curve A9F84132
device application |
Distribution
|
|
---|---|---|
range |
Acti 9
|
|
product name |
Acti 9 iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60H
|
|
poles description |
1P
|
|
number of protected poles |
1
|
|
[In] rated current |
32 A
|
|
network type |
DC
AC |
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 60…72 V DC conforming to EN/IEC 60947-2 20 kA Icu at 12…60 V DC conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
standards |
IEC 60947-2
IEC 60898-1 EN 60898-1 EN 60947-2 |
network frequency |
50/60 Hz
|
|
---|---|---|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
21 kA 50 % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz 21 kA 50 % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz 7.5 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 7500 A 75 % conforming to EN 60898-1 – 230 V AC 50/60 Hz 7500 A 75 % conforming to IEC 60898-1 – 230 V AC 50/60 Hz 15 kA 50 % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz 15 kA 50 % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz 15 kA 100 % conforming to EN 60947-2 – 72 V DC 15 kA 100 % conforming to IEC 60947-2 – 72 V DC 20 kA 100 % conforming to EN 60947-2 – 12…60 V DC 20 kA 100 % conforming to IEC 60947-2 – 12…60 V DC |
|
limitation class |
3 conforming to EN 60898-1
3 conforming to IEC 60898-1 |
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
2
|
|
height |
85 mm
|
|
width |
18 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.215 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
connections – terminals |
Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
3.5 N.m top or bottom
|
|
earth-leakage protection |
Without
|
₦3,999.00
Compare-
CHINT
CHINT NXM Series 2,3,4 Pole Moulded Case Circuit Breakers MCCB
The moulded case circuit breaker will provide protection for the circuit and equipment in case of overload, short circuit and under voltage condition occurred in the power distribution circuit. Besides, it can also provide protection of overload, short circuit and under voltage for the non-frequent start of motor
DESCRIPTION
- Compliance To IEC/EN60947-2
- Frame size: NXM series mould case circuit breaker: 63A, 125A, 160A, 250A, 400A, 630A, 800A, 1000A, 1250A, 1600A
- Release type: thermal magnetic fixed type; magnetic fixed type; electronic type
- Installation method: Fixed type; plug-in type
- Number of poles: 2P, 3P, 4P
- Rated operational voltage: Ue (VAC): 220, 415
- ICU: 25KA
- The brand-new electronic release Manage fault accurately Operate more efficiently and reliably
- Built-in busbar temperature sensor, to control every aspect. Select the most suitable frame size, increase the product cost performance and reduce costs of using.
- The brand-new electronic release, provide more accurate circuit protection. The all-new electronic release can deal with the hidden fault more accurately, with a more convenient parameters setting.
- Dual insulation design, for a more convenient maintenance. Enhance the insulating capacity of the product, allowing the accessories installation, which make the maintenance more safe and efficient.
- With a USB port for better human-machine interaction. Connected with PC devices through the USB port, lets you manage functions such as data reading, parameter setting, on-line detection and failure recording.
- Absolute adaptability, with steady and reliable operation in extreme conditions. -35°C/+70°operating temperature range.
SKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
Lisse – data socket – single RJ45 Cat 6 GGBL7071C6
Main range Lisseaesthetic name White mouldedproduct or component type Data socketdevice presentation Complete productdata socket type RJ45 – category 6colour tint Matt whitequantity per set Set of 10type of packing CartonComplementary number of gangs 1 gangcommunication network type RJ45fixing mode By screwsconnections – terminals Screw terminalsmaterial Urea (carbamide)type of installation Indoordepth 37 mmwidth 87 mmheight 87 mmnet weight 0.051 kgSKU: n/a -
CABLE AND CABLE MANAGEMENT, Electro, SINGLE CORE WIRE
Doncaster Cables 6mm Single Core – Red
Product Description
Manufactured to BS 6004:2012 Table 3
Annealed Stranded Copper Conductor / PVC Insulated / PVC Sheathed. 300/500V
Designed for use in light industrial and domestic wiring. These cables are particularly suited for installation as meter tails and are intended for fixed installation in dry or damp premises.
These cables can be installed in conduit, in cable trunking and in cable ducting. Or where there is deemed little risk of mechanical damage these cables can be clipped direct, on cable tray, embedded or in free air. These cables are not intended to be laid underground.
Product Details
Harmonisation Code Nominal Cross Sectional Area of Conductor (mm2) Nominal Stranding of Conductor (mm) Nominal Radial Thickness of insulation (mm) Nominal Radial Thickness of sheath (mm) Overall Diameter Lower Limit (mm) Overall Diameter Upper Limit (mm) Approximate Weight(kg/km) National Type 1.0 1 / 1.13 0.6 0.8 3.8 4.5 26 National Type 1.5 1 / 1.38 0.7 0.8 4.2 4.9 35 National Type 2.5 1 / 1.78 0.8 0.8 4.8 5.8 55 National Type 4.0 7 / 0.85 0.8 0.9 5.4 6.8 75 National Type 6.0 7 / 1.04 0.8 0.9 6.0 7.4 95 National Type 10.0 7 / 1.35 1.0 0.9 7.2 8.8 155 National Type 16.0 7 / 1.70 1.0 1.0 8.4 10.5 225 National Type 25.0 7 / 2.14 1.2 1.1 10.0 12.5 340 National Type 35.0 7 / 2.52 1.2 1.1 11.0 13.5 445 SKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
20A 250V 1 Gang Double Pole Switch with Neon and Earth KB31D20NE
Main range Vivaceproduct or component type Switchdevice short name KB31device presentation Complete mechanismComplementary switch function Double 1-way with earthactuator Rockerpilot light Neon indicator lampnumber of gangs 1 gangcolour tint Whitematerial Polycarbonate: grid plate
Polycarbonate: surround
Polycarbonate: baseprojecting depth 8 mmdevice mounting Flushmounting support Wall mountedfixing mode By screw M3.5fixing center 60.3 mmembedding depth 35 mmrated current 20 A at 250 V AC, inductive[Ue] rated operational voltage 250 V ACnetwork frequency 50 Hzcontacts material Brass and phosphor bronzeconnections – terminals pillar terminalterminal identifier L2
N2
N1
L1tightening torque 0.4 N.mclamping connection capacity 2.5 mm²
4 mm²width 87 mmheight 87 mmSKU: n/a