NX8 – MCB CHINT . ELECTRIC BOX 20way
The MCB CHINT NX8 plastic electrical cabinet box is compact, sturdy, and has a high finish.
Can be used as a wall cabinet or used as a floating cabinet due to its versatile design. There are error lights, power failure.
ABS plastic helps to withstand factors such as heat, sunlight, increasing the life of the cabinet. The lid of the cabinet is made of transparent PC plastic, making it easy to see the equipment inside. Available with 4-sided wiring hole.
Standard DIN Rail, convenient to connect and install equipment
Parameters of MCB CHINT NX8 . plastic electrical cabinet box
- Material: ABS/PC . plastic
- Type: Wall mounted plastic electrical cabinet
- Protection level: IP30
- Meets standards: IEC/EN 60439-3 (IEC/EN 60670-24)
- Application: in civil electricity, industrial electricity, solar power
₦82,500.00
Compare-
ELECTRICAL FITTINGS, Electro, INDOOR LIGHTS, LED LIGHTS, LIGHTING
LEDVANCE LED DOWNLIGHT 20WATT RECESSED LDECO 865K
ELECTRICAL FITTINGS, Electro, INDOOR LIGHTS, LED LIGHTS, LIGHTINGLEDVANCE LED DOWNLIGHT 20WATT RECESSED LDECO 865K
Product benefits
- Advanced functionality due to already included DALI driver
- DALI driver with individual luminaire current set-up already installed
- High luminous efficacy
- Energy savings up to 60 % (compared to luminaires that use CFL lamps)
- Very homogenous light
- Functional design
- Easy installation with fast connection
SKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 1P, 6 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84106
Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 1P, 6 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84106
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 1Pnumber of protected poles 1[In] rated current 6 Anetwork type AC
DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 60…72 V DC conforming to EN/IEC 60947-2
20 kA Icu at 12…60 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
IEC 60947-2
IEC 60898-1
EN 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 21 kA 50 % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 230 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 230 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz
15 kA 50 % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz
15 kA 100 % conforming to EN 60947-2 – 72 V DC
15 kA 100 % conforming to IEC 60947-2 – 72 V DC
20 kA 100 % conforming to EN 60947-2 – 12…60 V DC
20 kA 100 % conforming to IEC 60947-2 – 12…60 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.215 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection WithoutSKU: n/a -
Electro, LED LIGHTS, LIGHTING
PHILIPS Essential SmartBright LED Downlight G2 11W Philip
Essential SmartBright G2 LED Downlight is value for money product with high efficacy, good quality and reliability. It offers multiple configurations from 300lm to 2000lm output, to replace conventional downlight. It can be used for shopping mall, retail store, residential and office. It’s an ideal product family to distribute in trade market.
Benefits
- Reliability and safety: meets national and international regulation
- Diversity: One stop shopping with multiple choices of recess round, square as well as surface-mount to fit your dedicated applications
- Energy saving: High system efficacy with lower power consumption
- Easy to install with slim design
SKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 2P 4A C Miniature Circuit breaker A9F44204
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 2P 4A C Miniature Circuit breaker A9F44204
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 2Pnumber of protected poles 2[In] rated current 4 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 50 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 50 kA 100 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
25 kA 100 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a