Easy9 miniature circuit breaker- 2P – 6 A – C curve – 6000 A – 230 V EZ9F56206
range |
Easy9
|
|
---|---|---|
device application |
Distribution
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
Easy9 MCB
|
|
Poles |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
6 A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1 |
|
suitability for isolation |
Yes conforming to IEC 60898-1
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
220 V AC 50/60 Hz
400 V AC 50/60 Hz |
|
magnetic tripping limit |
5…10 x In
|
|
[Ics] rated service breaking capacity |
6 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Uimp] rated impulse withstand voltage |
4 kV conforming to IEC 60898-1
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Without
|
|
mounting mode |
Clip-on
|
|
mounting support |
DIN rail
|
|
9 mm pitches |
4
|
|
height |
81 mm
|
|
width |
36 mm
|
|
depth |
66.5 mm
|
|
colour |
Grey (RAL 7035)
|
|
mechanical durability |
10000 cycles
|
|
electrical durability |
4000 cycles
|
|
connections – terminals |
Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexible |
|
tightening torque |
2 N.m top or bottom
|
|
earth-leakage protection |
Without
|
₦7,600.00
Compare-
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONS
Ultimate Screwless flat plate – rocker plate switch – 3 gangs – black nickel GU1432BBN
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONSUltimate Screwless flat plate – rocker plate switch – 3 gangs – black nickel GU1432BBN
Main range of product Ultimaterange Ultimateaesthetic name Screwless flat plateproduct or component type Plate switchcontrol type Rockerswitch function 1-pole 2-wayrated current 16 AX at 230 V ACComplementary connections – terminals Screw terminalsmaterial Steelquantity per set Set of 1number of gangs 3 gangsdevice mounting Wall mountedheight 88 mmwidth 88 mmdepth 24 mmSKU: n/a -
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS
Schneider 10A 250V 2 Gang Bell Press Switch KB32BP
Main range Vivaceproduct or component type Switchdevice short name KB32device presentation Complete mechanismComplementary switch function 1-wayactuator Push-buttonnumber of gangs 2 gangscolour tint Whitematerial Polycarbonate: grid plate
Polycarbonate: surround
Nylon: baseprojecting depth 8 mmdevice mounting Flushmounting support Wall mountedfixing mode By screw M3.5fixing center 60.3 mmembedding depth 35 mmrated current 10 A at 250 V AC, inductive[Ue] rated operational voltage 250 V ACnetwork frequency 50 Hzcontacts material Brass and phosphor bronzeconnections – terminals pillar terminalterminal identifier COM
L2tightening torque 0.4 N.mclamping connection capacity <= 1.5 mm²width 86 mmheight 86 mmSKU: n/a -
ELECTRICAL INDUSTRIAL, TRANSFORMER
MEKSAN Transformer 50kVA 33/415kV
Meksan Transformer manufacture distribution and power transformer from 50 kVA up to 50 MVA. Our products are produced in accordance with the TS 267 and the IEC60076 standards. Our production is documented with the TSE (Türkish Standard Institue) standards confortmity, ISO 9001:2000 quality system and ISO 14001 environmental management system certificates.
SKU: n/a -
CABLE AND CABLE MANAGEMENT, Electro, SINGLE CORE WIRE
Doncaster Cables 4mm Single Core – Red
Product Description
Manufactured to BS 6004:2012 Table 3
Annealed Stranded Copper Conductor / PVC Insulated / PVC Sheathed. 300/500V
Designed for use in light industrial and domestic wiring. These cables are particularly suited for installation as meter tails and are intended for fixed installation in dry or damp premises.
These cables can be installed in conduit, in cable trunking and in cable ducting. Or where there is deemed little risk of mechanical damage these cables can be clipped direct, on cable tray, embedded or in free air. These cables are not intended to be laid underground.
Product Details
Harmonisation Code Nominal Cross Sectional Area of Conductor (mm2) Nominal Stranding of Conductor (mm) Nominal Radial Thickness of insulation (mm) Nominal Radial Thickness of sheath (mm) Overall Diameter Lower Limit (mm) Overall Diameter Upper Limit (mm) Approximate Weight(kg/km) National Type 1.0 1 / 1.13 0.6 0.8 3.8 4.5 26 National Type 1.5 1 / 1.38 0.7 0.8 4.2 4.9 35 National Type 2.5 1 / 1.78 0.8 0.8 4.8 5.8 55 National Type 4.0 7 / 0.85 0.8 0.9 5.4 6.8 75 National Type 6.0 7 / 1.04 0.8 0.9 6.0 7.4 95 National Type 10.0 7 / 1.35 1.0 0.9 7.2 8.8 155 National Type 16.0 7 / 1.70 1.0 1.0 8.4 10.5 225 National Type 25.0 7 / 2.14 1.2 1.1 10.0 12.5 340 National Type 35.0 7 / 2.52 1.2 1.1 11.0 13.5 445 SKU: n/a -