Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Fcircuit breaker name Easypact EZC100Fdevice application Distributionpoles description 3Pprotected poles description 3tnetwork type DC
ACnetwork frequency 50/60 Hz[In] rated current 100Ā A at 40Ā Ā°C[Ui] rated insulation voltage 690Ā V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6Ā kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Fbreaking capacity 25Ā kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25Ā kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
5Ā kA Icu at 125 V DC 1P conforming to IEC 60947-2
5Ā kA Icu at 250 V DC 2P conforming to IEC 60947-2
5Ā kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
10Ā kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
10Ā kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2
7.5Ā kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 12.5Ā kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
12.5Ā kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
2.5Ā kA at 125 V DC conforming to IEC 60947-2
2.5Ā kA at 250 V DC conforming to IEC 60947-2
2.5Ā kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
5Ā kA at 380 V AC 50/60 Hz conforming to IEC 60947-2
5Ā kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
3.75Ā kA at 440 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 20Ā A at 50Ā Ā°Cprotection type Short-circuit protection
Overload protectionpollution degree 3 conforming to IEC 60664-1
3 conforming to IEC 947-1SKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 1P 3A C Miniature Circuit breaker A9F44103
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 1P 3A C Miniature Circuit breaker A9F44103
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 1Pnumber of protected poles 1[In] rated current 3Ā Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 50Ā kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
50Ā kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
50Ā kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Ā kA Icu at 12…48 V DC conforming to EN/IEC 60947-2
6Ā kA Icu at 72 V DC conforming to EN/IEC 60947-2
6000Ā A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 240 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 50Ā kA 100Ā % conforming to EN/IEC 60947-2 – 12…60 V AC 50/60 Hz
50Ā kA 100Ā % conforming to EN/IEC 60947-2 – 100…133 V AC 50/60 Hz
50Ā kA 100Ā % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
6000Ā A 100Ā % conforming to EN/IEC 60898-1 – 240 V AC 50/60 Hz
15Ā kA 100Ā % conforming to EN/IEC 60947-2 – 12…48 V DC
6Ā kA 100Ā % conforming to EN/IEC 60947-2 – 72 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500Ā V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6Ā kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 2height 85Ā mmwidth 18Ā mmdepth 78.5Ā mmnet weight 0.125Ā kgcolour Whitemechanical durability 20000Ā cycleselectrical durability 10000Ā cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1ā¦25Ā mmĀ² rigid
Single terminal (top or bottom) 1ā¦16Ā mmĀ² flexiblewire stripping length 14Ā mm for top or bottom connectiontightening torque 2Ā N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
IC60H – miniature circuit breaker – 2P – 32A – C curve A9F84232
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSIC60H – miniature circuit breaker – 2P – 32A – C curve A9F84232
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 32Ā Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000Ā A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42Ā kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Ā kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Ā kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30Ā kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Ā kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
42Ā kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
IEC 60898-1
EN 60947-2
IEC 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15Ā kA 50Ā % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5Ā kA 50Ā % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
5Ā kA 50Ā % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15Ā kA 50Ā % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5Ā kA 50Ā % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
5Ā kA 50Ā % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
7500Ā A 75Ā % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500Ā A 75Ā % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
21Ā kA 50Ā % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
21Ā kA 50Ā % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
15Ā kA 100Ā % conforming to IEC 60947-2 – 72…125 V DC
15Ā kA 100Ā % conforming to EN 60947-2 – 72…125 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500Ā V AC 50/60 Hz conforming to EN 60947-2
500Ā V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6Ā kV conforming to EN 60947-2
6Ā kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85Ā mmwidth 36Ā mmdepth 78.5Ā mmnet weight 0.25Ā kgcolour Whitemechanical durability 20000Ā cycleselectrical durability 10000Ā cyclesconnections – terminals Single terminal (top or bottom) 1ā¦35Ā mmĀ² rigid
Single terminal (top or bottom) 1ā¦25Ā mmĀ² flexiblewire stripping length 14Ā mm for top or bottom connectiontightening torque 3.5Ā N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
-
ELECTRICAL INDUSTRIAL, WIRE CABLE TRAY & CABLE LADDER
Delta Cable Tray 300 x 100 x 3mtrs Hot Dip Galvanized
ELECTRICAL INDUSTRIAL, WIRE CABLE TRAY & CABLE LADDERDelta Cable Tray 300 x 100 x 3mtrs Hot Dip Galvanized
Metallic Delta Cable trays are manufactured for the smooth and easy pulling of cable from one point to another to BS EN 61537:2002.Ā We have designed the best cable trays, by taking care of cable loads and practical site problems.Ā Wherever possible all fitting are made of state of art single piece construction.Ā Slotting Patterns are in such a way that it enables the easy cutting and joining at any point without drilling at site.Ā Design allows greater cable filling capacity and smooth turning at bends.
SKU: Delta Cable Tray 50 x 100 x 3mtrs Hot Dip Galvanized-1-1 -
CIRCUIT BREAKERS
C120N – circuit breaker – 4P – 100A – C curve
Main range of product C120range Acti 9product name C120product or component type Miniature circuit-breakerdevice short name C120Ndevice application Distributionpoles description 4Pnumber of protected poles 4[In] rated current 100Ā A at 30Ā Ā°Cnetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000Ā A Icn at 230…400 V AC 50/60 Hz conforming to EN/IEC 60898-1
6Ā kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
20Ā kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Ā kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Ā kA Icu at <= 500 V DC conforming to EN/IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 380…415 V AC 50/60 Hz
<= 500 V DC
220…240 V AC 50/60 Hz
440 V AC 50/60 Hz
230…400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 7500Ā A 75Ā % conforming to EN/IEC 60898-1 – 230…400 V AC 50/60 Hz
4.5Ā kA 75Ā % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
7.5Ā kA 75Ā % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
15Ā kA 75Ā % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
10Ā kA 100Ā % conforming to EN/IEC 60947-2 – <= 500 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500Ā V AC 50/60 Hz conforming to EN/IEC 60947-2[Uimp] rated impulse withstand voltage 6Ā kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling ON/OFF indicationmounting mode Clip-onmounting support 35 mm symmetrical DIN railcomb busbar and distribution block compatibility NO9 mm pitches 12height 81Ā mmwidth 108Ā mmdepth 73Ā mmnet weight 0.82Ā kgcolour Whitemechanical durability 20000Ā cycleselectrical durability 5000Ā cycles conforming to IEC 60947-2connections – terminals Tunnel type terminals1ā¦50Ā mmĀ² rigid
Tunnel type terminals1.5ā¦35Ā mmĀ² flexiblewire stripping length 15Ā mmtightening torque 3.5Ā N.mearth-leakage protection Separate blockSKU: n/a