Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
IC60H – miniature circuit breaker – 1P – 16A – C curve A9F84116
device application |
Distribution
|
|
---|---|---|
range |
Acti 9
|
|
product name |
Acti 9 iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60H
|
|
poles description |
1P
|
|
number of protected poles |
1
|
|
[In] rated current |
16Â A
|
|
network type |
DC
AC |
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000Â A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 42Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15Â kA Icu at 60…72 V DC conforming to EN/IEC 60947-2 20Â kA Icu at 12…60 V DC conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
standards |
IEC 60947-2
IEC 60898-1 EN 60947-2 EN 60898-1 |
network frequency |
50/60 Hz
|
|
---|---|---|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
21Â kA 50Â % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
7.5Â kA 50Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz 21Â kA 50Â % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz 7.5Â kA 50Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 7500Â A 75Â % conforming to EN 60898-1 – 230 V AC 50/60 Hz 7500Â A 75Â % conforming to IEC 60898-1 – 230 V AC 50/60 Hz 15Â kA 50Â % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz 15Â kA 50Â % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz 15Â kA 100Â % conforming to EN 60947-2 – 72 V DC 15Â kA 100Â % conforming to IEC 60947-2 – 72 V DC 20Â kA 100Â % conforming to EN 60947-2 – 12…60 V DC 20Â kA 100Â % conforming to IEC 60947-2 – 12…60 V DC |
|
limitation class |
3 conforming to EN 60898-1
3 conforming to IEC 60898-1 |
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to EN 60947-2
6Â kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
2
|
|
height |
85Â mm
|
|
width |
18Â mm
|
|
depth |
78.5Â mm
|
|
net weight |
0.215Â kg
|
|
colour |
White
|
|
mechanical durability |
20000Â cycles
|
|
electrical durability |
10000Â cycles
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14Â mm for top or bottom connection
|
|
tightening torque |
2Â N.m top or bottom
|
|
earth-leakage protection |
Without
|
₦10,800.00
Compare-
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit breaker, Easy9, 3P, 32 A, C curve, 6000 A EZ9F56332
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit breaker, Easy9, 3P, 32 A, C curve, 6000 A EZ9F56332
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 3Pnumber of protected poles 3[In] rated current 32Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000Â A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000Â A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50 Hz[Ue] rated operational voltage 220 V AC 50/60 Hz
400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 6height 81 mmwidth 54 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² flexible
Tunnel type terminal (top or bottom) 1…35 mm² rigidtightening torque 3.5 N.m top or bottomSKU: n/a -
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC100N4060 Circuit breaker Easypact EZC100N – TMD – 60 A – 4 poles 3d
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC100N4060 Circuit breaker Easypact EZC100N – TMD – 60 A – 4 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Ncircuit breaker name Easypact EZC100Ndevice application Distributionpoles description 4Pprotected poles description 3tnetwork type DC
ACnetwork frequency 50/60 Hz[In] rated current 100 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Nbreaking capacity 10Â kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
5Â kA Icu at 125 V DC 1P conforming to IEC 60947-2
5Â kA Icu at 250 V DC 2P conforming to IEC 60947-2
5Â kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
15Â kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2
18Â kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 5Â kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5Â kA at 125 V DC conforming to IEC 60947-2
2.5Â kA at 250 V DC conforming to IEC 60947-2
2.5Â kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5Â kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
12.5Â kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
9Â kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 60 A at 50 °Cprotection type Short-circuit protection
Overload protectionpollution degree 3 conforming to IEC 60947Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 8500Â cycleselectrical durability Category A: 1500Â cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 25Â mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 130Â mmwidth 100Â mmdepth 60Â mmSKU: n/a -
ELECTRICAL FITTINGS, Electro, INDOOR LIGHTS, LED LIGHTS, LIGHTING
LEDVANCE LED DOWNLIGHT 20WATT RECESSED LDECO 865K
ELECTRICAL FITTINGS, Electro, INDOOR LIGHTS, LED LIGHTS, LIGHTINGLEDVANCE LED DOWNLIGHT 20WATT RECESSED LDECO 865K
Product benefits
- Advanced functionality due to already included DALI driver
- DALI driver with individual luminaire current set-up already installed
- High luminous efficacy
- Energy savings up to 60 % (compared to luminaires that use CFL lamps)
- Very homogenous light
- Functional design
- Easy installation with fast connection
SKU: n/a -
ELECTRICAL INDUSTRIAL, TRANSFORMER
BETA 750KVA/33/0.415V COPPER/COPPER WINDING TRANSFORMER
Produced within a power range between 10 – 100.000 kVA , up to 170 kV high voltage level, three phase or single phase, oil immersed, ONAN, ONAF, OFWF, with Off-Load or On-Load Tap Changer, used both external and internal.
Dimensions of transformer conservator are determined and designed after several heat calculations of the oil stored in expansion tank and oil level changes by heat.
Being open to atmosphere, oil pressure changes continuously in Conservator Type Transformers due to thermal effects and exchange of air is dehumidified via air breather silicagel.SKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
32A 1 Gang Full-Flat Double Rocker Switch with Neon, White E8431D32_WE
LIGHT SWITCHES & ELECTRICAL SOCKETS32A 1 Gang Full-Flat Double Rocker Switch with Neon, White E8431D32_WE
Main range ZENceloproduct or component type Switchload type Resistivecolour tint Whitecover frame colour tint WhiteComplementary device mounting Flush
Surfacerated current 32 A at 250 V AC 50/60 Hzlocal signalling Indicator light, neon (amber)number of gangs 1 gangmaterial Polycarbonate + GF 20 %: grid plate
Polycarbonate: base
Polycarbonate: cover
Polycarbonate: surroundconnections – terminals Brass rod terminalsembedding depth 22Â mmwidth 87Â mmheight 87Â mmdepth 30.2Â mmSKU: n/a -
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC100N4020 – Circuit breaker Easypact EZC100N – TMD – 20 A – 4 poles 3d
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC100N4020 – Circuit breaker Easypact EZC100N – TMD – 20 A – 4 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Ncircuit breaker name Easypact EZC100Ndevice application Distributionpoles description 4Pprotected poles description 3tnetwork type DC
ACnetwork frequency 50/60 Hz[In] rated current 100 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Nbreaking capacity 10Â kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
5Â kA Icu at 125 V DC 1P conforming to IEC 60947-2
5Â kA Icu at 250 V DC 2P conforming to IEC 60947-2
5Â kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
15Â kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2
18Â kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 5Â kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5Â kA at 125 V DC conforming to IEC 60947-2
2.5Â kA at 250 V DC conforming to IEC 60947-2
2.5Â kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5Â kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
12.5Â kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
9Â kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 20 A at 50 °Cprotection type Short-circuit protection
Overload protectionpollution degree 3 conforming to IEC 60947Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 8500Â cycleselectrical durability Category A: 1500Â cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 25Â mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 130Â mmwidth 100Â mmdepth 60Â mmSKU: n/a
There are no reviews yet.