IC60H – miniature circuit breaker – 1P – 40A – C curve A9F84140
device application |
Distribution
|
|
---|---|---|
range |
Acti 9
|
|
product name |
Acti 9 iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60H
|
|
poles description |
1P
|
|
number of protected poles |
1
|
|
[In] rated current |
40Â A
|
|
network type |
AC
DC |
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000Â A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 42Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15Â kA Icu at 60…72 V DC conforming to EN/IEC 60947-2 20Â kA Icu at 12…60 V DC conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
standards |
IEC 60947-2
IEC 60898-1 EN 60898-1 EN 60947-2 |
network frequency |
50/60 Hz
|
|
---|---|---|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
21Â kA 50Â % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
7.5Â kA 50Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz 21Â kA 50Â % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz 7.5Â kA 50Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 7500Â A 75Â % conforming to EN 60898-1 – 230 V AC 50/60 Hz 7500Â A 75Â % conforming to IEC 60898-1 – 230 V AC 50/60 Hz 15Â kA 50Â % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz 15Â kA 50Â % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz 15Â kA 100Â % conforming to EN 60947-2 – 72 V DC 15Â kA 100Â % conforming to IEC 60947-2 – 72 V DC 20Â kA 100Â % conforming to EN 60947-2 – 12…60 V DC 20Â kA 100Â % conforming to IEC 60947-2 – 12…60 V DC |
|
limitation class |
3 conforming to EN 60898-1
3 conforming to IEC 60898-1 |
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to EN 60947-2
6Â kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
2
|
|
height |
85Â mm
|
|
width |
18Â mm
|
|
depth |
78.5Â mm
|
|
net weight |
0.215Â kg
|
|
colour |
White
|
|
mechanical durability |
20000Â cycles
|
|
electrical durability |
10000Â cycles
|
|
connections – terminals |
Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexible |
|
wire stripping length |
14Â mm for top or bottom connection
|
|
tightening torque |
3.5Â N.m top or bottom
|
|
earth-leakage protection |
Without
|
₦4,999.00
Compare-
ELECTRICAL INDUSTRIAL, TRANSFORMER
BETA 300KVA/33/0.415V COPPER/COPPER WINDING TRANSFORMER
Produced within a power range between 10 – 100.000 kVA , up to 170 kV high voltage level, three phase or single phase, oil immersed, ONAN, ONAF, OFWF, with Off-Load or On-Load Tap Changer, used both external and internal.
Dimensions of transformer conservator are determined and designed after several heat calculations of the oil stored in expansion tank and oil level changes by heat.
Being open to atmosphere, oil pressure changes continuously in Conservator Type Transformers due to thermal effects and exchange of air is dehumidified via air breather silicagel.SKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
32A 1 Gang Full-Flat Double Rocker Switch with Neon, Sliver Bronze E8431D32_SZ
LIGHT SWITCHES & ELECTRICAL SOCKETS32A 1 Gang Full-Flat Double Rocker Switch with Neon, Sliver Bronze E8431D32_SZ
Main range ZENceloproduct or component type Switchload type Resistivecolour tint Silver bronzecover frame colour tint Silver bronzeComplementary device mounting Surface
Flushrated current 32 A at 250 V AC 50/60 Hzlocal signalling Indicator light, neon (amber)number of gangs 1 gangmaterial Polycarbonate + GF 20 %: grid plate
Polycarbonate: base
Polycarbonate: cover
Polycarbonate: surroundconnections – terminals Brass rod terminalsembedding depth 22Â mmwidth 87Â mmheight 87Â mmdepth 30.2Â mmSKU: n/a -
Electro, SOCKETS, SOCKETS & SWITCHES
BG BG860 – TELEVISION 1 GANG CO-AXIAL SOCKET
BG Electrical 860 is a 1 Gang Co-Axial Socket.
Part of the comprehensive range of BG Electrical White Rounded Edge switches and sockets, BG 860 features a slim profile, rounded edges and screw covers for a sleeker appearance.
Features of BG Electrical 860 1 Gang Co-Axial Socket Include:
- 1 Gang Co-Axial Socket
- Finish: Plastic
- Colour: White
- Screw Covers
- Back box required: 25mm min
- Plate Height: 86mm
- Plate Width: 86mm
- Overall Depth: 27mm
- Profile: Slim
- Product Type: Co-Axial Socket
- Standards: BS 3041 & BS 5733
- 30 Year Guarantee
SKU: n/a -
Electro, SOCKETS & SWITCHES, SWITCHES
BG BRASS GEORGIAN DOUBLE POLE SWITCH WITH NEON 20 AMP
BG NBG31 Brass Georgian Double Pole Switch with Neon 20 Amp
AT A GLANCE…- Top quality Brass finish – lightly lacquered to prevent finger marks
- Matching Brass rocker switch & slim line LED indicator
- No visible plastic around switches
- Specification: 20 amp, double pole (BS EN 60669-1)
- Requires a 25mm metal wall box
- Supplied with colour coded fixing screws
SKU: n/a -
ELECTRICAL INDUSTRIAL, TRANSFORMER
BETA 500KVA/11/0.415V COPPER/COPPER WINDING TRANSFORMER
Produced within a power range between 10 – 100.000 kVA , up to 170 kV high voltage level, three phase or single phase, oil immersed, ONAN, ONAF, OFWF, with Off-Load or On-Load Tap Changer, used both external and internal.
Dimensions of transformer conservator are determined and designed after several heat calculations of the oil stored in expansion tank and oil level changes by heat.
Being open to atmosphere, oil pressure changes continuously in Conservator Type Transformers due to thermal effects and exchange of air is dehumidified via air breather silicagel.SKU: n/a -
Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC100F3050 – Circuit breaker Easypact EZC100F – TMD – 50 A – 3 poles 3d
Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC100F3050 – Circuit breaker Easypact EZC100F – TMD – 50 A – 3 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Fcircuit breaker name Easypact EZC100Fdevice application Distributionpoles description 3Pprotected poles description 3tnetwork type DC
ACnetwork frequency 50/60 Hz[In] rated current 100 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Fbreaking capacity 25Â kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
5Â kA Icu at 125 V DC 1P conforming to IEC 60947-2
5Â kA Icu at 250 V DC 2P conforming to IEC 60947-2
5Â kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
10Â kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
10Â kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2
7.5Â kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 12.5Â kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
12.5Â kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
2.5Â kA at 125 V DC conforming to IEC 60947-2
2.5Â kA at 250 V DC conforming to IEC 60947-2
2.5Â kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
5Â kA at 380 V AC 50/60 Hz conforming to IEC 60947-2
5Â kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
3.75 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 50 A at 50 °Cprotection type Overload protection
Short-circuit protectionpollution degree 3 conforming to IEC 60664-1
3 conforming to IEC 947-1Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 8500Â cycleselectrical durability Category A: 1500Â cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 25Â mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 130Â mmwidth 75Â mmdepth 60Â mmSKU: n/a
There are no reviews yet.