Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 2P 2A C Miniature Circuit breaker A9F44202
range |
Acti 9
|
|
---|---|---|
product name |
Disbo iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60N
|
|
poles description |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
2Â A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
50Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
50Â kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 6Â kA Icu at 100…133 V DC conforming to EN/IEC 60947-2 6000Â A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1 |
|
utilisation category |
Category A conforming to EN/IEC 60947-2
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
440 V AC 50/60 Hz
|
|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
50Â kA 100Â % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
50Â kA 100Â % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz 50Â kA 100Â % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz 25Â kA 100Â % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz 6000Â A 100Â % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz 6Â kA 100Â % conforming to EN/IEC 60947-2 – 100…133 V DC |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz
|
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to EN/IEC 60947-2
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Clip-on
|
|
mounting support |
Rail
|
|
9 mm pitches |
4
|
|
height |
85Â mm
|
|
width |
36Â mm
|
|
depth |
78.5Â mm
|
|
net weight |
0.25Â kg
|
|
colour |
White
|
|
mechanical durability |
20000Â cycles
|
|
electrical durability |
10000Â cycles
|
|
provision for padlocking |
Padlockable
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14Â mm for top or bottom connection
|
|
tightening torque |
2Â N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
standards |
EN/IEC 60898-1
EN/IEC 60947-2 |
|
---|---|---|
IP degree of protection |
IP20 conforming to IEC 60529
|
|
pollution degree |
3 conforming to EN/IEC 60947-2
|
|
tropicalisation |
2 conforming to IEC 60068-1
|
|
relative humidity |
95 % at 55 °C
|
|
ambient air temperature for operation |
-35…70 °C
|
|
ambient air temperature for storage |
-40…85 °C
|
₦11,960.00
Compare-
-
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 2P 3A C Miniature Circuit breaker A9F44203
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 2P 3A C Miniature Circuit breaker A9F44203
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 2Pnumber of protected poles 2[In] rated current 3Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 50Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
50Â kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
50Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
25Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
6Â kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000Â A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 50Â kA 100Â % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
50Â kA 100Â % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
50Â kA 100Â % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
25Â kA 100Â % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000Â A 100Â % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockEnvironment standards EN/IEC 60947-2
EN/IEC 60898-1IP degree of protection IP20 conforming to IEC 60529pollution degree 3 conforming to EN/IEC 60947-2tropicalisation 2 conforming to IEC 60068-1relative humidity 95 % at 55 °Cambient air temperature for operation -35…70 °Cambient air temperature for storage -40…85 °CSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 Residual Current Circuit Breaker – 2P – 63 A – 300 mA – AC type – 230 V EZ9R64263
Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 Residual Current Circuit Breaker – 2P – 63 A – 300 mA – AC type – 230 V EZ9R64263
Main range of product Easy9product or component type Residual current circuit breaker (RCCB)device short name Easy9 RCCBPoles 2Pneutral position Left[In] rated current 63 Anetwork type ACearth-leakage sensitivity 300 mAearth-leakage protection time delay Instantaneousearth-leakage protection class Type ACrated breaking and making capacity 500 Arated conditional short-circuit current Easy9 MCB: 4500 A 63 AComplementary device location in system Outgoernetwork frequency 50 Hz[Ue] rated operational voltage 230 V AC 50 Hzresidual current tripping technology Voltage dependent[Ui] rated insulation voltage 440 V AC[Uimp] rated impulse withstand voltage 4 kVsurge current 250 Acontact position indicator Yescontrol type Togglemounting mode Clip-onmounting support DIN railcomb busbar and distribution block compatibility Top: YES9 mm pitches 4height 82 mmwidth 36 mmdepth 72 mmcolour Grey (RAL 7035)mechanical durability 5000 cycleselectrical durability AC: 2000 cycles 230 V AC 50 Hzconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexibletightening torque 2.5 N.m top or bottommarket segment Residential
Small commercialEnvironment standards IEC 61008-1product certifications GOST-R
CE
EACIP degree of protection IP20pollution degree 2 conforming to IEC 61008-1tropicalisation 2relative humidity 95 % at 55 °Cambient air temperature for operation -25…60 °Cambient air temperature for storage -40…85 °CSKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
1 Gang 350VA, 50Hz Full-Flat Universal Dimmer with LED, Sliver Bronze E8431EPD4_SZ
LIGHT SWITCHES & ELECTRICAL SOCKETS1 Gang 350VA, 50Hz Full-Flat Universal Dimmer with LED, Sliver Bronze E8431EPD4_SZ
Main product or component type Dimmerlocal signalling On: indicator light, LED (amber)
Off: indicator light, LED (blue)additional information With memory push[Ue] rated operational voltage 220…240 V AC 50 Hzmaterial Brass: metal parts
Polycarbonate: plastic part
Steel: metal partscover frame colour tint Silver bronzeComplementary wiring device mounting Surface
Flushclamping connection capacity 2 x 4 mm² for solid cable(s)
2 x 4 mm² for stranded cable(s)
3 x 2.5 mm² for solid cable(s)
3 x 2.5 mm² for stranded cable(s)rated operational power in VA 350 VAnumber of gangs 1 gangload type LV halogen
Incandescent lampembedding depth 6Â mmwidth 87Â mmheight 87Â mmdepth 35Â mmSKU: n/a
There are no reviews yet.